Product Description
Place of Origin: Jiangsu, China (Mainland)
Model: CPF-100CX, CPF-100D1X, CPF-100D2X, option
Capacity: 100 grams per hour
Certification: ISO9001, CE Marked
EINECS No. 233-162-8
CAS NO. 10049-04-4
Control Mode: Manual / Flow Control / Residual clo2 Control, option
Installation Method: Wall-mounted or vertical
Power Supply: 220V/50Hz
Detailed Photos
Product Parameters
Main parameters:1. Operating voltage: AC220V plus or minus 10%2. Working temperature: -5 ~ 50 degrees Celsius
3. Relative humidity: 80%4. Maximum pressure of water-pipe-line: <0.7Mpa5. There should be no strong electromagnetic field interference around the equipment.6. Function: Manual / Flow Auto Control / Residual ClO2 Control Low liquid level alarm function Timing start / stop function
Alarm remote transfer
Chemical Equation & Raw Chemicals 5 NaClO2 + 4HCl = 4ClO2 + 5NaCl + 2H2O
NaClO2: industrial sodium chlorite (purity≥78% ) , dilute to use
Activator: industrial first grade compound hydrochloric acid (purity≥31%) or other weak acid or strong acid, dilute to use Two raw chemicals of NaClO2 and HCl are to be inhaled into the reactor proportionally by two metering pumps, in which produce quantitative high-purity ClO2 solution, and then to be dosed directly in the water tank or pressured water pipe together with the dilution water.
The highest outlet pressure of ClO2 solution is 0.40Mpa. Raw chemicals conversion rate is higher than 90%. The dosage of ClO2 can be adjusted manually or automatically by receiving 4-20mA signal sent by flow rate or residual ClO2 sensor.